C-GIS

C-GIS

GSR6-12/24/40.5 environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS)

GSR6-12/24/40.5 environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS)

Features

GSR6-12/24/40.5 environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS) is independently developed by our company and use dry air (Air) or nitrogen (N2) It is an environmentally friendly gas-insulated metal-enclosed switchgear with insulating medium.

Product Overview

GSR6-12/24/40.5 environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS) is independently developed by our company and uses dry air (Air) Or environmentally friendly gas-insulated metal-enclosed switchgear with nitrogen (N2) as the insulating medium. The product technology level is domestically leading and internationally advanced. It is a new generation of medium-voltage complete switchgear that integrates vacuum arc extinguishing technology, APG sealing technology, gas insulation technology and interface insulation technology. The product has passed the formal test verification and new product technical appraisal by the national authoritative testing agency, obtained Duoxiang national invention patent and utility model patent, and has independent intellectual property rights. Products can be widely used in various important power distribution and transformation systems of the national economy, such as transmission and substation networks, urban power supply networks, large industrial and mining enterprises, petrochemical industry, metallurgy, urban rail transit and other fields.

The product adopts modular design and can be combined according to different design plans. The product adopts a sealed pressure system. All high-voltage live parts of the main circuit are sealed in a stainless steel gas box and are not affected by the environment. It has the characteristics of reliable operation, small space occupation, and maintenance-free.



Technical Parameters

                                                             ItemUnit                                     Parameter
Rated voltagekV122440.5
Rated frequencyHz505050
Rated currentA1250/2500/3150/40001250/2500/3150/40001250/2500
Rated insulation levelPower frequency withstand voltage (phase to phase and ground)kV426595
Power frequency withstand voltage (isolation fracture)kV4879118
Lightning impulse withstand voltage (phase to phase and ground)kV75125185
Lightning impulse withstand voltage (isolated fracture)kV85145215
Rated power frequency withstand voltage of auxiliary circuitkV222
Rated short-time withstand currentkA25/31.5/40
Rated short circuit durations333
Rated peak withstand currentkA63/80/10063/80/10063/80
Rated short-circuit breaking currentkA25/31.5/4025/31.5/4025/31.5
Rated short-circuit making current (peak)kA63/80/10063/80/10063/80
Rated cable charging breaking currentA2531.550
Rated operating sequence
O-0.3s-CO-3min-CO
Insulating gas
Dry air or nitrogen
Mechanical lifeCircuit breakertimes100001000010000
Three-position switch500050005000
Dry air or nitrogen rated pressure (abs.20℃)Rated inflation pressure (abs.20℃)Mpa0.140.140.14
Minimum inflation pressure (abs.20℃)0.120.120.12
Protection levelSealed boxLevelIP67IP67IP67
Switchgear enclosureIP4XIP4XIP4X
Dry air relative leakage rate%/year≤0.1≤0.1≤0.1
Rated power supply voltage of auxiliary circuitVDC48/110/220 AC220


Product size

Rated voltageRated current of main busCabinet typeWidth (mm)Depth (mm)Height (mm)
12/24kV1250AIncoming line, segmentation, isolation, outgoing line60015002400
Main device (PT)100015002400
Measuring cabinetAir box type600/100015002400
Air type600/100015002400
2500/3150/4000AIncoming line, segmentation, isolation, outgoing line, bus equipment (PT)100018502400
40.5kV1250AIncoming line, segmentation, isolation, outgoing line90022002400
Master setting (PT)100022002400
2500AIncoming line, segmentation, isolation, outgoing line, bus equipment (PT)100022002400





Features

1

Adopting internationally advanced concepts, world-class production, testing methods, laser welding, laser cutting, helium leak detection and other equipment.

2

The primary component of the product adopts a fully sealed design, which is completely sealed in a sealed air box welded by stainless steel plates. It is filled with dry air or nitrogen of a certain pressure as the insulating medium. The protection level reaches IP67, which completely avoids the impact of the external environment and climate on the switch cabinet. It can operate reliably in harsh environments such as basements, plateaus, frozen soil, coastal areas, and humidity, and is maintenance-free.

3

The product can be operated manually or electrically. The operating mechanism is mature and reliable, and it has complete mechanical and electrical interlocking, which can effectively prevent personal injury and equipment damage that may be caused by misoperation. 3. The product can be operated manually or electrically. The operating mechanism is mature and reliable, and it has complete mechanical and electrical interlocking, which can effectively prevent personal injury and equipment damage that may be caused by misoperation.

4

The product design has a compact structure. Compared with the traditional air insulated switch cabinet, the volume is significantly reduced, and the floor area is reduced by 30%-70%, which improves space utilization and effectively reduces the comprehensive cost of the project.

5

Microprocessor-based protection and system technology integrates protection, control, measurement, detection, and communication functions to achieve distribution network automation and digitalization requirements, and can be completely unattended.

Product usage environment

Altitude: ≤5000m (when the equipment operating altitude exceeds 1000m, special instructions are required)

Ambient temperature: maximum temperature +50℃, minimum temperature -25℃, 24h average value ≤35℃

Ambient humidity : 24h average relative humidity ≤95% , the average monthly relative humidity is ≤90%

Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system is ≤1.6kV

Installation environment : There are no explosive and corrosive gases in the surrounding air, and there is no frequent severe vibration or impact in the installation site.


Note: Use beyond the above Environmental conditions, please contact us